Battery Walk in Test Chambers
Battery Walk in Test Chambers
- Batch product testing
- Precise temperature control
- High quality accessories
- Multilingual User Interface
- 12 months warranty
- Long service life
- Energy-saving design
- High-quality cooling system
- Stable operation
As a walk in chamber manufacturer with extensive experience, KOMEG provides temperature humidity controlled chamber solutions for various industries, supported by numerous established cases.
Our walk in test chambers have a wide temperature range (-60ºC to 150℃) and humidity range (20% to 98% RH). You can choose the desired temperature/humidity range to meet the testing requirements of different products and standards. Additionally, you can customize parameters such as temperature change rate, size, color, and more.
If the product you want to test has the risk of fire or explosion, such as batteries, battery packs, etc., you need to customize explosion-proof safety devices, like this battery walk in test chamber. Basic explosion-proof devices include explosion-proof windows, explosion-proof chains and explosion-proof pressure relief port. Other safety devices can also be added, such as gas detectors, alarm lights, smoke detectors, fire detectors, air exhauster, fire extinguishers, and sprinklers.
Features
- SUS304 Stainless Steel Plate: Welded inside for a durable structure.
- Customized Buttons: Commonly used buttons for easy operation.
- Insulation: Rigid polyurethane foam, flame retardant grade B2.
- Cooling System: Mechanical compression refrigeration with water cooling.
- Safety Protection Devices: Various devices to ensure the normal operation of the machine.
- Color Touch Screen Controller: Offers comprehensive functions and simple operation.
- Circuit Design: Neat design for easy maintenance.
- Communication Ports: RS485, Ethernet communication port, and USB download port.
- Standard Accessories: glass window, cable port, lighting, and more.
Model | KWH | ||||||
| 4 | 8 | 10 | 15 | 20 | 45 | |
Inner chamber size(mm) | W | 2000 | 2000 | 2040 | 2500 | 2500 | 5000 |
| H | 2000 | 2000 | 2100 | 3000 | 2000 | 3000 |
| D | 1000 | 2000 | 2100 | 2000 | 4000 | 3000 |
Temperature range | High temperature: 80℃,150℃ Low temperature: -60 ºC, -50 ºC, -40 ºC , -30 ºC, -20 ºC , -10 ºC, 0 ºC | ||||||
Temperature deviation | ≤±2.0℃ | ||||||
Temperature fluctuation | ±0.5℃ | ||||||
Temperature uniformity | ≤2.0℃ | ||||||
Humidity range | 20% to 98% RH | ||||||
Humidity deviation | ±3.0%RH(˃75%RH)±5.0%RH(≤75%RH) | ||||||
Humidity fluctuation | ±2.0%RH | ||||||
Humidity uniformity | ±3.0%RH(empty) | ||||||
Heating rate | +20ºC~ +80ºC within 60 min | ||||||
Cooling rate | +20ºC~-60ºC/-50ºC/-40ºC/-30ºC/-20ºC/-10ºC, within 120/90/60min | ||||||
Power | 380V AC 3Ø 50Hz |